Power Source: 120 VAC 60Hz 4 Amp Dedicated Circuit
Battery Type: Two 12Vdc 4Ah Sealed Lead Acid Batteries Connected in Series for up to 24 Hours Standby Operation or two 12Vdc 7Ah Sealed Lead Acid Batteries Connected in Series for 60 Hours Standby Operation
Special Application NACs:
Programmable Non Power Limited. 1 Class “A” (Style Z) or 2 Class “B” (Style Y)
Field Selectable
Class A Ratings: 12 Volts DC @ 1.75 Amps or 24 Volts DC @ 1 Amp
Class B Ratings: x12 Volts DC @ 1.75 Amps Each or 24 Volts DC @ 1 Amp Each
Regulated NACs: Programmable Non-power Limited. 1 Class “A” (Style Z) or 2 Class “B” (Style Y) Field Selectable
Class A Ratings: 12 DC @ 175 Milliamps Each 24 Volts DC @ 100 Milliamps
Class B Ratings: 12 Volts DC @ 175 Milliamps Each or 24 Volts DC @ 100 Milliamps
Dry Contact Alarm Relays:
4 N.O. Non-programmable Rated 30 Vdc @ 1 Amp. Resistive
2 Form “C” Programmable Rated 30 Vdc @ 1 Amp. Resistive
Dry Contact Trouble Relays:
2 N.O. Non-programmable Rated 24 Vdc @ 1 Amp. Resistive
2 N.C. Non-programmable Rated 24 Vdc @ 1 Amp. Resistive
Auxiliary Output: Current 300 ma. Max Coil Resistance 14.6 Ohms
Transceiver Operating Frequency: 900 MHz Band
Antenna Type: Omni
Enclosure: Powder Coated 16 Gauge Steel
Testing: Follow the CP3000 CWSI Manual and NFPA 72 or Local Requirements
Transmission: Complies to FCC Part 15
In addition to the standard features the CP-3000D offers:
Point Specific Fire Alarm Reporting
Pinpoint Off-Site Annunciation
SIA Format Event Reporting
Supervised Dialer Interface
Test Mode Automatically Times out in 4 Hours
Compatible with Keltron SDACT Communicator
Height 17” | Width 17” | Depth 3.25” | Weight 29 lbs.
|